32050106M: Boiler violation issued
Building violation issued details
| Location | 198 9 AVENUE, MANHATTAN |
|---|---|
| Issue date | May 22, 2006 |
| ECB violation number | 32050106M |
| Infractions | B4A: Failure to maintain boiler |
| Is active | No |
| Violation type | Boiler |
| Description | 50,48A/FULTON V.T. BOILER 15HP NB 51986 GAS 1987/50-IMPROPER ARRANGEMENT OF THE BLOWDOWN VALVES. INSTALL A SCREW TYPE (SLOW) VALVE AT OUTLETEND OF THE BLOWDOWN LINE/48A-DIRTY GAUGE GLASS,REPLACE |
| Severity | Moderate |
| Compliance status | Good reinspection |
Added to EveryBlock on May 22, 2006.