32047119Y: Boiler violation issued
Building violation issued details
| Location | 87-20 256 STREET, QUEENS |
|---|---|
| Issue date | March 3, 2006 |
| ECB violation number | 32047119Y |
| Infractions | B4B: Failure to maintain boiler (A) (hazardous) |
| Is active | Yes |
| Violation type |
Boiler
Violations related to boilers, a common heating device where water is converted to steam. Common infractions relate to improper maintenance (dirty boilers) and lack of fire door on a boiler room, which is a hazardous condition. |
| Description | CEASE USE. 7B/50A/50B/50C/50D/50E. 50A- EXPANSION TANK PIPING CORRODED 50B- LWCO MUST BE RELOCATED 50C- BOILER BEING FED INTO SAFETY RELIEFVALVE PIPING 50D- INSOLATION AROUND BOILER MISSING 50E- CHIMNEY ROTTED |
| Severity | High |
| Compliance status | Overdue complete record |
Added to EveryBlock on March 3, 2006.