32047896Z: Boiler violation issued

Building violation issued details

Location 85-08 GRAND AVENUE, QUEENS
Issue date July 20, 2005
ECB violation number 32047896Z
Infractions B4A: Failure to maintain boiler

Inspectors in the Boiler Division issue this type of violation. This violation is issued either as a result of a complaint, as a result of a scheduled inspection for an application, or as part of a review of previously issued violations. It is the most common type of all boiler violations issued by inspectors. The violation is used when any part of the boiler is not in a safe condition. The owner is responsible at all times for the safe maintenance of the building and its facilities. The violation can be "Cured" if no hearing has yet been held and it is not a hazardous or second offense violation.

Is active Yes
Violation type Boiler

Violations related to boilers, a common heating device where water is converted to steam. Common infractions relate to improper maintenance (dirty boilers) and lack of fire door on a boiler room, which is a hazardous condition.

Description 50A/50B FULTON V.T. BOILER, 10HP, NB 66275, GAS 1992 50A) NO DRAIN LINE ON THE GAUGE GLASS ASSEMBLY. 50B) IMPROPER ARRANGEMENT OF THE BLOWDOWN VALVES INSTALL A SLOW VALVE AT THE OUTLET END OF THE BLOWDOWN LINE.
Severity Moderate
Compliance status No complete record

Added to EveryBlock on July 20, 2005.